Products
FG2000
FG2000inverter is a series of high performance and low noise inverter independently developed by WindSun with a brand-new idea and a simple design. With increased stability, this series has a raft of practical and advanced functions for operation and control, like simple vector-based PI controller, light load oscillation suppression, detection of input and/or output phase loss, re-starting at the tracked rotation speed, flexible input/output terminals, online changes of parameters, auto-identification if signal transmission failures, storage of shut-down and power-off parameters, wobbulator control and RS485 control. WindSun provides equipment manufacturers and the end users with highly integrated solutions which are greatly helpful for lowering system purchase and operation cost and increasing system reliability.
Item | Standard | |
Input | Rated voltage of power supply | Power supply voltage ±20, 50-60 Hz±5%, voltage unbalance rate <3% |
Output | Rated voltage | The maximum output voltage is identical to the input power supply voltage. |
Rated current | 100% continuous rated current | |
Over-load capacity | Type G: 1 minute for 150% of rated current and 2 seconds for 180% of rated current Type P: 1 minute for 120% of rated current and 2 seconds for 150% of rated current | |
Output frequency | 0 Hz~500 Hz | |
Main control functions | Control approach | V/F control, vector control |
Frequency resolution | Digital setting: 0.01 Hz Analog setting: 0.05 Hz | |
Start frequency | 0 Hz~20 Hz | |
Torque compensation | Manual torque compensation 0.1%~30.0% | |
V/F curve | Five modes: Constant torque V/F curve, 1 user-defined multiple-segment V/F curve and 3 torque-decrease curve ( to the power of 2, to the power of 1.7 and to the power of 1.2) | |
Acceleration and deceleration curve | Two modes: Straight-line and S-curve; Seven kinds of times available for acceleration and deceleration in (minute/second), with 60,000 minutes at a minimum | |
DC injection braking | Start frequency of DC injection braking: 0~15.00 Hz Braking time: 0~60.0 seconds Braking current: 0~80% | |
Variable-speed operation | Achieved through built-in PLC or control terminal | |
Wobble frequency | Preset frequency and adjustable central frequency | |
Automatic voltage regulation (AVR) | The output voltage is kept constant when grid voltage changes | |
Automatic energy-saving operation | V/F curve is automatically optimized to save energy according to the load | |
Automatic current limiter | The current when inverter is working is limited automatically to avoid frequent over-currents that may cause trip. | |
Communication function | Be equipped with RS485 standard port and support MODBUS protocol | |
Operation command channels | Keyboard, control terminals and series port (RS485) | |
Frequency setting channel | Potentiometer that simulates a keyboard, keys , function code setting, series port and terminal UP/DOWN, setting of simulated voltage, simulated current and voltage/current combination | |
Input functions | Digit input channels | For models up to 380V/30 kW and 220V: 5 channels for inputting programmable digital quantities |
For models at 380V/37-400 kW and 660V: 8 channels for inputting programmable digital quantities | ||
Analog input channels | For models up to 380V/30 kW and 220V: 2 channels for inputting analog signals 1 channel at 0~10V and 1 at 0~10V/0~20 mA, which can be switched. | |
For models at 380V/37-400 kW and 660V: 3 channels for inputting analog signals 2 channels at 0~10V and 1 at 0~10V/0~20 mA, which can be switched. | ||
Output functions | Digit output channels | For models up to 380V/30 kW and 220V: 1 open collector output, 1 relay output, 1 0~20 k HZ pulse output |
For models at 380V/37-400 kW and 660V: 2 open collector outputs, 2 relay outputs, 1 0~20 k HZ pulse output | ||
Analog output channels | For models up to 380V/30 kW and 220V: 1 channel for outputting analog signals 1 channel at 0~10V and 1 at 0~10V/0~20 mA, which can be switched. | |
For models at 380V/37-400 kW and 660V: 2 channels for outputting analog signals 2 channels at 0~10V and 1 at 0~10V/0~20 mA, which can be switched. | ||
Operation panel | LED digit display | Inverter parameters can be displayed or set. |
Key lock | All keys can be locked | |
Parameter copy | Function code parameters between inverter can be copied by using a remote keyboard. | |
Protection functions | Many protection functions: Short circuit, over-current, over-load, over-voltage, under-voltage, phase loss, over-heat, external faults | |
Options | Remote keyboard, remote operation box, braking unit | |
Environment | Working place | Indoor, free from direct sunshine, dust, corrosive atmosphere, oil mist and steam |
Elevation | Lower than 1000 m (Rated parameters must be lowered when it is used at an elevation higher than 1000 m) | |
Ambient temperature | -10℃~+40℃ | |
Humidity | Lower than 90% RH without condensation | |
Vibration | Smaller than 5.9 m/S2 (0.6G) | |
Storage temperature | -20℃~+60℃ | |
Structure | IP grade | IP20 |
Cooling | Forced air cooling | |
Mounting method | Wall-mounting or floor-standing |